Power Factor Correction Calculator
Calculate the capacitor bank kVAr required to improve electrical power factor from an existing value to a target value.
PF
PF
Target power factor must be higher than the existing power factor.
Required Capacitor Bank
—
Reactive compensation required to reach the entered target power factor.
Required compensation
—
Existing reactive power
—
Reactive power after correction
—
Apparent power before correction
—
Apparent power after correction
—
Apparent power reduction
—
Existing power factor
—
Target power factor
—
Method:
Required reactive compensation is calculated from:
Qc =
P ×
[tan(φ₁) − tan(φ₂)]
where:
φ₁ = cos⁻¹(PF₁)
φ₂ = cos⁻¹(PF₂)
P is real power, PF₁ is the existing power factor and PF₂ is the target power factor.
Existing reactive power:
Q₁ = P × tan(φ₁)
Corrected reactive power:
Q₂ = P × tan(φ₂)
Apparent power before correction:
S₁ = P ÷ PF₁
Apparent power after correction:
S₂ = P ÷ PF₂
The calculated kVAr is the theoretical capacitive reactive power required at the stated operating load. Actual capacitor-bank selection normally uses available standard kVAr steps and should account for load variation, switching strategy, harmonics, utility requirements and equipment ratings.
Avoid unnecessary overcorrection. Systems with variable loads may require automatically switched capacitor banks rather than a fixed bank.