Solar String Size Calculator

Solar

Solar String Size Calculator

Calculate the minimum and maximum number of solar panels that can be connected in series per inverter string.

Solar Panel
V
V
Find Voc and Vmp on the solar module datasheet.
Inverter / MPPT
V
V
Use the inverter manufacturer’s DC input specifications.
Cold-Weather Check
°C
%/°C
Enter the Voc temperature coefficient exactly as shown on the module datasheet. It is normally a negative value.
Panels Per String
—
Preliminary series-string range based on the panel, inverter and temperature conditions entered.
Maximum Panels Per String —
Minimum Panels Per String —
Cold-Corrected Panel Voc —
Maximum Cold String Voc —
String Connection Diagram
Minimum String
Maximum String
How it is calculated: Panel open-circuit voltage is corrected for the entered minimum temperature using the module’s Voc temperature coefficient. Maximum panels per string = inverter maximum DC voltage ÷ cold-corrected panel Voc, rounded down. Minimum panels per string = inverter minimum MPPT voltage ÷ panel Vmp, rounded up. The maximum-string calculation helps prevent excessive DC voltage during cold conditions. The minimum-string result is a simplified STC-based MPPT check. Final design should also verify the inverter’s full MPPT operating range at expected module temperatures, maximum input current, short-circuit-current limit and manufacturer string-design requirements.